Graham Alarm Monitoring
The Independent Dealer's Best Choice

ULC Report

 
Date of Inspection
Date of Inspection
1. This is to certify that the monitored system has been tested and inspected in accordance with CAN ULC-5561, Standard for Installation and Services for Fire Signal Receiving Centres and Systems Section 11, Periodic Inspections and Tests, and these records document the results of testing performed.
2. The monitored system is fully functional:
OR The monitored system has deficiencies noted on the page attached:
4. A copy of this report will be given to the owner or representative for this building.
Phone Number of Service Personnel Conducting Test
Phone Number of Service Personnel Conducting Test
Signal Transmitting Unit Test — YES - Tested Correctly || NO - Did NOT Test Correctly || N/A - Feature NOT available
Power On Visual Indicator
Common Visual Trouble Signal
Common Audible Trouble Signal
Main Power Supply Failure Signal
Alarm Signal Operation
Input Circuit Trouble Operation
Main Power Supply to Emergency Power Supply Transfer
Trouble Signal Indicating Failure of Primary Path of Communications Received Within 180 Secs
Restoral of Trouble Signal Indicating Failure of Primary Path of Communication Received
Trouble Signal Indicating Failure of Secondary Backup Path of Communications Received Within 180 Secs
Restoral of Trouble Signal Indicating Failure of Secondary Backup Path of Communication Received
Signal Transmitting Unit — YES - Tested Correctly || NO - Did NOT Test Correctly || N/A - Feature NOT available
Input Circuit Designations Correctly Identified
Verified Correct Connected Field Devices
Plug In Components and Modules
Plug In Cables Securely In Place
Cleanliness Observed
Fuses In Accordance With Manufacturers Specification
Termination Points from Wiring To Field Devices Secure
Signal Transmitting Unit Lock
Power Supply Inspection — YES - Tested Correctly || NO - Did NOT Test Correctly || N/A - Feature NOT available
Fused As Per Manufacturers Marked Rating Of The System
Adequate To Meet The Requirements of The System
Annual Battery Inspection Report
Correct Battery Type as Recommended by Manufacturer
Correct Rating as Determined by Battery Calculations
Battery Charging Voltage Present
Battery Charging Current Present
Battery Will Provide 24hr Standby
Battery Inspected for Physical Damage
Terminals Clamped Tightly
Battery Terminals Cleaned and Lubricated
Adequate Ventilation
Within Manufacturers Rated Life Cycle
Disconnect Caused Trouble Signal